New Acoustics Building at NTT Musashino R&D Center

Bibliographic Information

Other Title
  • NTT武蔵野研究開発センタ新音響実験棟について

Search this article

Description

The acoustics building at NTT's Musashino R&D center has been replaced. The new building includes an anechoic room and a reverberation room. In designing the rooms, the specifications were improved, as were acoustic characteristics, such as the soundproof characteristics, to handle the increasing environmental noise from the urban area that has developed around the R&D center. In the anechoic room, sound absorber wedges with a 50-Hz cutoff frequency were installed, and deviation within±0.5 dBs from the inverse square law has been realized in the range up to 20,000 Hz. The background noise level in the room was-2 dB(A) when the air-conditioners were in operation. In the reverberation room, the reverberation time was about 29 and 15 seconds, respectively at the 125-Hz and 500-Hz bands. The background noise level in the room was 18 dB(A).

Journal

  • Technical report of IEICE. EA

    Technical report of IEICE. EA 96 (576), 41-48, 1997-03-14

    The Institute of Electronics, Information and Communication Engineers

Citations (1)*help

See more

References(5)*help

See more

Details 詳細情報について

  • CRID
    1574231877151535360
  • NII Article ID
    110003284111
  • NII Book ID
    AN10164817
  • Text Lang
    ja
  • Data Source
    • CiNii Articles

Report a problem