- Regarding the recording of “Research Data” and “Evidence Data”
New Acoustics Building at NTT Musashino R&D Center
-
- KIYOHARA Kenji
- NTT Human Interface Laboratories
-
- KANEDA Yutaka
- NTT Human Interface Laboratories
-
- KOJIMA Junji
- NTT Human Interface Laboratories
Bibliographic Information
- Other Title
-
- NTT武蔵野研究開発センタ新音響実験棟について
Search this article
Description
The acoustics building at NTT's Musashino R&D center has been replaced. The new building includes an anechoic room and a reverberation room. In designing the rooms, the specifications were improved, as were acoustic characteristics, such as the soundproof characteristics, to handle the increasing environmental noise from the urban area that has developed around the R&D center. In the anechoic room, sound absorber wedges with a 50-Hz cutoff frequency were installed, and deviation within±0.5 dBs from the inverse square law has been realized in the range up to 20,000 Hz. The background noise level in the room was-2 dB(A) when the air-conditioners were in operation. In the reverberation room, the reverberation time was about 29 and 15 seconds, respectively at the 125-Hz and 500-Hz bands. The background noise level in the room was 18 dB(A).
Journal
-
- Technical report of IEICE. EA
-
Technical report of IEICE. EA 96 (576), 41-48, 1997-03-14
The Institute of Electronics, Information and Communication Engineers