PMU based monitoring and estimation of interarea power oscillation for Singapore-Malaysia interconnection power system
説明
This paper proposes a PMU (phasor measurement unit) based monitoring and estimation scheme of power system small-signal stability in Singapore-Malaysia interconnection power system through a 50-Hz and 500 kV transmission line. Two PMUs are installed in the power system interconnection network of Singapore-Malaysia. One PMU is located in Singapore and the other one in Malaysia (Penang). Both PMUs measure the single-phase voltage phasor. The data filtering technique based on Fast Fourier Transform (FFT) is employed to extract oscillation data for single mode. Finally, some analysis results of monitoring and estimation of Singapore-Malaysia interconnected power system based on application practice of the CampusWAMS are presented and analyzed.
収録刊行物
-
- 2010 Conference Proceedings IPEC
-
2010 Conference Proceedings IPEC 476-480, 2010-10-01
IEEE