An influence of voltage sag duration on nonutility generator's shaft torque

説明

An influence of the voltage sag magnitude and duration on nonutility generator's mechanical shaft torque is investigated by simulations using the Electromagnetic Transients Program (ATP-EMTP). Various types of fault are simulated, changing the fault point, the number of faulted phases and the voltage phase angle at the moment of fault occurring. From the simulation results, it becomes clear that the high-speed static switchgear is effective for the stable operation of the in-house generation systems and the critical loads, which are subjected to the voltage sag.

収録刊行物

詳細情報 詳細情報について

問題の指摘

ページトップへ