熱源・空調システムの最適制御技術の導入に向けた研究 (第2報)冷却水入口温度の設定値最適化の導入と実測による効果検証

DOI

書誌事項

タイトル別名
  • Study on the Introduction of Optimal Operation for an HVAC System - Part 2: Introduction of Optimal Operation Regarding Cooling Water Temperature Set Point, and Verification of Energy-Saving Effects by Actual Measurement

抄録

<p>The aim of this study is to develop optimal operation technology for an HVAC system. The authors derived an approximately straight line to decide the optimal set point for the cooling water temperature from the exterior wet-bulb temperature. It was confirmed that energy consumption could be reduced using the approximately straight line by actual measurement. The authors verified the accuracy of the simulation tool that is used to build the optimal operation method.</p>