Evaluation of Thermal Interruption Capability in SF₆ Gas Circuit Breakers with Re-ignition Voltage and its Application to Experimental Design
-
- Urai Hajime
- Hitachi Research Laboratory, Hitachi, Ltd.
-
- Ooshita Youichi
- Hitachi Research Laboratory, Hitachi, Ltd.
-
- Koizumi Makoto
- Hitachi Research Laboratory, Hitachi, Ltd.
-
- Tsukushi Masanori
- Japan AE Power Systems Corporation
書誌事項
- タイトル別名
-
- Evaluation of Thermal Interruption Capability in SF<sub>6</sub> Gas Circuit Breakers with Re-ignition Voltage and its Application to Experimental Design
この論文をさがす
説明
Thermal interruption characteristics of SF6 gas circuit breakers were investigated by voltage measurements around current zero. We found that re-ignition peak voltage in the case of an interruption failure could effectively indicate the thermal interruption capability. The efficiency of interruption to puffer pressure could also be evaluated by analyzing the dependency of re-ignition peak voltage on puffer pressure. This technique was applied to experimental design based on the Taguchi method. We successfully optimized the balance of the puffer pressure build-up performance and thermal interruption efficiency to puffer pressure. Finally we demonstrated that a small size research circuit breaker with self-blast interrupter was able to successfully clear the 90% short line fault interruption duty corresponding to 50kA rating in the thermal interruption region.
収録刊行物
-
- 電気学会論文誌B(電力・エネルギー部門誌)
-
電気学会論文誌B(電力・エネルギー部門誌) 132 (5), 407-414, 2012
一般社団法人 電気学会
- Tweet
キーワード
詳細情報 詳細情報について
-
- CRID
- 1390282679579938048
-
- NII論文ID
- 10030605420
-
- NII書誌ID
- AN10136334
-
- BIBCODE
- 2012IJTPE.132..407U
-
- ISSN
- 13488147
- 03854213
-
- NDL書誌ID
- 023776289
-
- 本文言語コード
- en
-
- データソース種別
-
- JaLC
- NDL
- Crossref
- CiNii Articles
-
- 抄録ライセンスフラグ
- 使用不可