- Study on Energy Consumption and Indoor Thermal Environment of Floor Heating System using Exhausted Heat from PEFC-CGS
- PEFC CGS ト オンスイシキ ユカダンボウ ノ ヘイヨウ コウカ ニ カンスル ケンキュウ ショウエネルギー コウカ ト シツナイ オンネツ カンキョウ ニ ツイテ
この論文をさがす
抄録
We have been developed the numerical simulation program to calculate the primary energy consumption of housing Polymer Electrolyte Fuel Cell Co-Generation System(PEFC-CGS) combined with floor heating of warm water type. In this program, the floor heating has been modeled with the piping pitch of warm water by using the fin efficiency. The indoor temperature has been controlled by Predicted Mean Vote(PMV) for over minus 0.5. As the results of this simulation, it is clarified that the floor heating has had effected the indoor by thermal radiation from floor surface and that the primary energy consumption has been reduced up to 5% in winter when PEFC-CGS is combined with the floor heating of warm water type.
収録刊行物
-
- 都市・建築学研究
-
都市・建築学研究 11 127-136, 2007-01-15
九州大学大学院人間環境学研究院都市・建築学部門