インバータ電源大量導入時においても電圧変動を抑制可能なPV曲線に基づくインバータ力率選定法の提案

書誌事項

タイトル別名
  • Power Factor Control for Inverters under High Penetration of Distributed Generation
  • —Proposal of a Method to Select a Power Factor based on <i>P-V</i> Curves—

抄録

<p>The paper proposes a method to select a power factor for an inverter of distributed power generation systems to keep appropriate voltage of a power system with the high penetration of inverter-interfaced generation. The increase of inverter-interfaced power sources, such as wind and photovoltaic power generation, arouses concerns on the voltage fluctuations in a power system. While constant power factor control of an inverter has been studied as a means to stabilize the voltage of a power system, there still remains room to improve the control. The proposed method in the paper selects the power factor based on the R/X ratio of the looking-back impedance into the interconnected power system. By normalizing the related variables, a general formula is derived for the power factor; and the resultant relationship between the apparent power and voltage of an inverter becomes identical irrespective of the R/X ratio with the control. Sample studies show that, by operating an inverter with the power factor, voltage fluctuations are effectively suppressed even for a power system with the high penetration of inverter-interfaced generation.</p>